Safety
This page collects the hazards that apply to installing, operating, and servicing the TankerTherm 123. Each hazard is also repeated as a safety notice at the step where it applies, so a technician who goes straight to one procedure still sees it.
Safety notices in this manual
| Notice | Used for |
|---|---|
WARNING |
A hazard that can cause death or serious injury — electric shock, burns from hot glycol or hot surfaces. |
CAUTION |
A hazard that can damage the equipment or cause minor injury — for example, starting the boiler before the air purge, or dry-running the refill pump. |
IMPORTANT |
A required step or condition that is not itself a hazard — for example, obtaining a Warranty Request Number before shipping parts. |
NOTE |
Background information that helps you understand a procedure or reading. |
TIP |
Practical advice that makes a task easier. |
Qualified personnel
-
Electrical installation and any work at the boiler face must be performed by a licensed electrician in compliance with local electrical codes.
-
Calibration and setpoint changes on the PLC are password-protected and change how the unit protects itself. Make them only if you understand the procedure — see PLC Calibration and PLC Controls and Setpoints.
Electrical hazards
The unit is supplied at 480 V or 600 V 3-phase, depending on SKU. The Stop and E-Stop buttons stop the unit’s outputs; they do not remove power from the supply terminals in the boiler. Only the upstream main disconnect does that.
|
High voltage at the boiler face — lock out before touching any wire
Before touching any wire at the boiler face: open the upstream main disconnect, lock it out and tag it out, and verify zero voltage with a properly rated meter. This work must be performed by a qualified electrician. The boiler face exposes the 480 V or 600 V 3-phase supply next to the low-voltage control wiring. Contact with energized 3-phase conductors can be fatal. |
Lockout/tagout
Before any work at the boiler face or on the supply wiring:
-
Open the upstream main disconnect.
-
Lock out and tag out the disconnect per site procedure.
-
Verify zero voltage at the boiler with a properly rated meter.
This applies to:
-
Power Supply Connections — connecting the supply and ground conductors
-
Startup & First Heat Cycle — disconnecting and reconnecting the boiler control wire for the air purge
-
Any troubleshooting that involves electrical components, leaking glycol, or smoke — see Troubleshooting
Hot surfaces and hot glycol
|
Hot surfaces — personal protective equipment required
The distribution manifold and piping operate at up to 190°F (88°C). Always wear heat-resistant gloves when engaging ball valves or connecting/disconnecting tanker lines. Direct contact with the manifold can cause severe burns. |
-
Stop the system and let the glycol cool before opening any strainer, fitting, or drain — see Periodic Maintenance.
-
The Tank Temp probe sits in a compression fitting on the storage tank. Withdrawing it with the tank above approximately 20 % lets coolant flow out of the sensor hole — see Temperature probe calibration.
Pressure
-
A 30 PSI pressure relief valve protects the boiler. Do not plug, cap, or adjust it.
-
The PLC stops the refill pump if refill-line pressure exceeds the Max Pressure setting (default 25.0 PSI). Do not raise this setting toward 30 PSI — see Refill pressure calibration.
Protective interlocks
Do not bypass or disable any of the following. Each is described in Specifications — Protection summary.
-
LWCO (Low-Water Cut-Off) sensor — disables the boiler if the storage tank is critically low
-
ECO high-temperature limit switch on the boiler
-
30 PSI pressure relief valve
-
Fill Time Limit and Refill Pressure cutoffs on the refill pump
-
E-Stop button on the manifold control panel
Emergency stop
The red E-Stop button on the manifold control panel stops the circulation pump, the boiler, and the refill pump, and latches the alarm strobe. The PLC banner reads Operator ESTOP. The E-Stop does not de-energize the unit — use the main disconnect for that.
To recover, release the E-Stop, press Reset, and press Start — see Resolution — Operator ESTOP.
Equipment-damage hazards
These hazards damage the unit rather than injure people. Each is a CAUTION at the step where it applies.
| Hazard | Consequence | Where it applies |
|---|---|---|
Starting the boiler before the air purge is complete |
Boiler damage, not covered by warranty |
|
Running the refill pump dry |
The gear-type refill pump can be destroyed by approximately 20 minutes of cumulative dry running. Repeatedly pressing Reset after a |
|
Rotating a bulkhead fitting while tightening |
Damaged internal connections; may void the warranty |
|
Pulling out crating blocking strips carelessly |
Damaged distribution plumbing |
|
Replacing a Remote Output Box fuse with a higher rating |
Damaged PLC output drivers or 12 V DC converter |