Temperature Control

The boiler’s onboard digital controller holds the glycol at a configured target temperature, measured at the boiler outlet. The PLC enables and disables the boiler but does not regulate its temperature. To run slightly hotter or cooler than the configured target, apply an offset of up to ±10 °F on the boiler controller’s faceplate — no configuration menus are involved.

Adjusting the setpoint offset

Adjustment range

  • Maximum: +10°F (+5°C) above configured target

  • Minimum: −10°F (−5°C) below configured target

  • Adjustment resolution: 1°F / 1°C

Adjustment procedure

  1. Press + or - on the boiler controller.

  2. The display shows 0 and blinks, indicating zero offset from configured target.

  3. Continue pressing + or - to dial in the desired offset.

  4. Stop pressing the buttons. The new value blinks for 5 seconds and is then applied.

  5. The display returns to standard view, showing the new effective target temperature.

Reviewing the current offset

Press + or - again to display the currently applied offset. You can re-adjust from this value.

Offset persistence

The offset is persistent across power cycles. To return to the configured target, adjust the offset back to 0.

How the boiler holds the setpoint

The boiler controller is configured to hold a fixed target temperature using the boiler’s two heating stages. The target does not vary with outdoor temperature.

  1. On a call for heat from the Start button, the circulating pump starts.

  2. The boiler activates the number of stages required to reach and maintain the configured target temperature at the boiler outlet.

  3. Stage rotation occurs on an equal time period basis to distribute wear evenly across heating stages.

Tank temperature reading and remote monitoring

The PLC reads tank coolant temperature from a dedicated probe (independent of the boiler controller). You can view or transmit this reading in two ways:

The tank-temperature probe can be field-zero-calibrated against an ice-water reference — see Temperature probe calibration.