Temperature Control
The boiler’s onboard digital controller holds the glycol at a configured target temperature, measured at the boiler outlet. The PLC enables and disables the boiler but does not regulate its temperature. To run slightly hotter or cooler than the configured target, apply an offset of up to ±10 °F on the boiler controller’s faceplate — no configuration menus are involved.
Adjusting the setpoint offset
Adjustment range
-
Maximum: +10°F (+5°C) above configured target
-
Minimum: −10°F (−5°C) below configured target
-
Adjustment resolution: 1°F / 1°C
Adjustment procedure
-
Press + or - on the boiler controller.
-
The display shows
0and blinks, indicating zero offset from configured target. -
Continue pressing + or - to dial in the desired offset.
-
Stop pressing the buttons. The new value blinks for 5 seconds and is then applied.
-
The display returns to standard view, showing the new effective target temperature.
How the boiler holds the setpoint
The boiler controller is configured to hold a fixed target temperature using the boiler’s two heating stages. The target does not vary with outdoor temperature.
-
On a call for heat from the Start button, the circulating pump starts.
-
The boiler activates the number of stages required to reach and maintain the configured target temperature at the boiler outlet.
-
Stage rotation occurs on an equal time period basis to distribute wear evenly across heating stages.
Tank temperature reading and remote monitoring
The PLC reads tank coolant temperature from a dedicated probe (independent of the boiler controller). You can view or transmit this reading in two ways:
-
On the PLC Home and Status screens — see PLC Controller Overview.
-
As a 0–10 V analog output representing 0–200 °F, intended for connection to a remote monitoring or data-acquisition system. The scale is linear: each volt represents 20 °F, so tank temperature (°F) = output voltage × 20. See Remote Output Box — Temperature output and Temperature Analog Output.
The tank-temperature probe can be field-zero-calibrated against an ice-water reference — see Temperature probe calibration.