Temperature Control

Glycol temperature is controlled in two places:

  • The PLC Tank Heat thermostat watches the storage-tank temperature. When the tank rises above its Target, the PLC holds the boiler off; when the tank cools, the PLC lets the boiler run again.

  • The boiler’s onboard digital controller holds the glycol at a configured target temperature, measured at the boiler outlet, whenever the PLC allows the boiler to run.

Use the Tank Heat Target to choose how hot the storage tank is kept. Use the boiler controller’s offset to trim the boiler outlet temperature by up to ±10 °F.

Tank Heat thermostat (PLC)

To open the Tank Heat screen: press F2, enter the password, select Controls, then press the next arrow twice (Cooling Fan → LCD Screen Heat → Tank Heat).

The screen shows the live tank temperature and three settings:

Setting Range Factory setting Meaning

Target

80–195 °F

195 °F

Tank temperature above which the PLC holds the boiler off.

Hysteresis

1–50 °F

10 °F

How far the tank must cool below Target before the boiler is allowed to run again.

Delay

Up to 60 s

1 s

How long the tank must stay below Target minus Hysteresis before the boiler is allowed to run again. Keeps a momentary dip from restarting the boiler.

How it works during a heating session:

  1. The boiler runs until the tank temperature rises above Target.

  2. The PLC then holds the boiler off. The circulation pump keeps running, so the connected tankers still receive hot glycol. The banner reads Enabled - Target Reached, the Heat indicator on the Home screen is off, and the manifold indicator lamp shows a 1-second steady blink.

  3. When the tank temperature has been below Target minus Hysteresis for the Delay time, the PLC allows the boiler to run again and the banner returns to Enabled-Heating.

For example, with a Target of 150 °F and a Hysteresis of 10 °F, the boiler is held off above 150 °F and runs again once the tank has cooled below 140 °F.

At the factory settings

The factory Target of 195 °F is above the 190 °F design operating temperature, so the thermostat does not normally interrupt heating and the boiler controller sets the working temperature. Lower the Target to hold the storage tank at a lower temperature.

Changing a Tank Heat setting

  1. Open the Tank Heat screen.

  2. Tap the value to change. The on-screen number pad opens.

  3. Enter the new value and confirm. The PLC accepts only values inside the range shown above.

  4. Press F1 to return to the Home screen.

Adjusting the setpoint offset (boiler controller)

To run slightly hotter or cooler than the boiler controller’s configured target, apply an offset of up to ±10 °F on the boiler controller’s faceplate — no configuration menus are involved.

Adjustment range

  • Maximum: +10°F (+5°C) above configured target

  • Minimum: −10°F (−5°C) below configured target

  • Adjustment resolution: 1°F / 1°C

Adjustment procedure

  1. Press + or - on the boiler controller.

  2. The display shows 0 and blinks, indicating zero offset from configured target.

  3. Continue pressing + or - to dial in the desired offset.

  4. Stop pressing the buttons. The new value blinks for 5 seconds and is then applied.

  5. The display returns to standard view, showing the new effective target temperature.

Reviewing the current offset

Press + or - again to display the currently applied offset. You can re-adjust from this value.

Offset persistence

The offset is persistent across power cycles. To return to the configured target, adjust the offset back to 0.

How the boiler holds the setpoint

The boiler controller is configured to hold a fixed target temperature using the boiler’s two heating stages. The target does not vary with outdoor temperature.

  1. On a call for heat — the unit is started and the tank is not above the Tank Heat Target — the circulating pump runs and the PLC enables the boiler.

  2. The boiler activates the number of stages required to reach and maintain the configured target temperature at the boiler outlet.

  3. Stage rotation occurs on an equal time period basis to distribute wear evenly across heating stages.

Tank temperature reading and remote monitoring

The PLC reads tank coolant temperature from a dedicated probe (independent of the boiler controller). The Tank Heat thermostat uses this reading. You can view or transmit it in two ways:

The tank-temperature probe can be field-zero-calibrated against an ice-water reference — see Temperature probe calibration. Because the Tank Heat thermostat acts on this reading, keep the probe calibrated.