Temperature Control
Glycol temperature is controlled in two places:
-
The PLC Tank Heat thermostat watches the storage-tank temperature. When the tank rises above its Target, the PLC holds the boiler off; when the tank cools, the PLC lets the boiler run again.
-
The boiler’s onboard digital controller holds the glycol at a configured target temperature, measured at the boiler outlet, whenever the PLC allows the boiler to run.
Use the Tank Heat Target to choose how hot the storage tank is kept. Use the boiler controller’s offset to trim the boiler outlet temperature by up to ±10 °F.
Tank Heat thermostat (PLC)
To open the Tank Heat screen: press F2, enter the password, select Controls, then press the next arrow twice (Cooling Fan → LCD Screen Heat → Tank Heat).
The screen shows the live tank temperature and three settings:
| Setting | Range | Factory setting | Meaning |
|---|---|---|---|
Target |
80–195 °F |
195 °F |
Tank temperature above which the PLC holds the boiler off. |
Hysteresis |
1–50 °F |
10 °F |
How far the tank must cool below Target before the boiler is allowed to run again. |
Delay |
Up to 60 s |
1 s |
How long the tank must stay below Target minus Hysteresis before the boiler is allowed to run again. Keeps a momentary dip from restarting the boiler. |
How it works during a heating session:
-
The boiler runs until the tank temperature rises above Target.
-
The PLC then holds the boiler off. The circulation pump keeps running, so the connected tankers still receive hot glycol. The banner reads
Enabled - Target Reached, the Heat indicator on the Home screen is off, and the manifold indicator lamp shows a 1-second steady blink. -
When the tank temperature has been below Target minus Hysteresis for the Delay time, the PLC allows the boiler to run again and the banner returns to
Enabled-Heating.
For example, with a Target of 150 °F and a Hysteresis of 10 °F, the boiler is held off above 150 °F and runs again once the tank has cooled below 140 °F.
|
At the factory settings
The factory Target of 195 °F is above the 190 °F design operating temperature, so the thermostat does not normally interrupt heating and the boiler controller sets the working temperature. Lower the Target to hold the storage tank at a lower temperature. |
Adjusting the setpoint offset (boiler controller)
To run slightly hotter or cooler than the boiler controller’s configured target, apply an offset of up to ±10 °F on the boiler controller’s faceplate — no configuration menus are involved.
Adjustment range
-
Maximum: +10°F (+5°C) above configured target
-
Minimum: −10°F (−5°C) below configured target
-
Adjustment resolution: 1°F / 1°C
Adjustment procedure
-
Press + or - on the boiler controller.
-
The display shows
0and blinks, indicating zero offset from configured target. -
Continue pressing + or - to dial in the desired offset.
-
Stop pressing the buttons. The new value blinks for 5 seconds and is then applied.
-
The display returns to standard view, showing the new effective target temperature.
How the boiler holds the setpoint
The boiler controller is configured to hold a fixed target temperature using the boiler’s two heating stages. The target does not vary with outdoor temperature.
-
On a call for heat — the unit is started and the tank is not above the Tank Heat Target — the circulating pump runs and the PLC enables the boiler.
-
The boiler activates the number of stages required to reach and maintain the configured target temperature at the boiler outlet.
-
Stage rotation occurs on an equal time period basis to distribute wear evenly across heating stages.
Tank temperature reading and remote monitoring
The PLC reads tank coolant temperature from a dedicated probe (independent of the boiler controller). The Tank Heat thermostat uses this reading. You can view or transmit it in two ways:
-
On the PLC Home, Status and Tank Heat screens — see PLC Controller Overview.
-
As a 0–10 V analog output representing 0–200 °F, intended for connection to a remote monitoring or data-acquisition system. The scale is linear: each volt represents 20 °F, so tank temperature (°F) = output voltage × 20. See Remote Output Box — Temperature output and Temperature Analog Output.
The tank-temperature probe can be field-zero-calibrated against an ice-water reference — see Temperature probe calibration. Because the Tank Heat thermostat acts on this reading, keep the probe calibrated.