What Changed Since Software v2.1

This page is for anyone who knows a unit on PLC software v2.1 and is now working with v2.2 — for example after a software update. It lists what is different. The rest of this manual describes v2.2 as it is.

To check which software a unit runs, read the Version line on the Status screen — see Which manual matches my unit?.

Added

What What it means for you

PURGE screen

The air purge is now run from the PLC. You no longer open the boiler cover or disconnect the boiler control wire. See Startup & First Heat Cycle.

Tank Heat thermostat

A new screen sets a tank-temperature Target (80–195 °F). Above the target the PLC holds the boiler off and the banner reads Enabled - Target Reached. See Temperature Control.

Refill pressure sensor fault

A broken wire, an unplugged connector or a failed refill pressure sensor now stops the unit with the banner REFILL SENSOR FAULT and the alarm strobe. Before, it went unnoticed. See Troubleshooting.

Three new system states

Purging, Enabled - Target Reached and REFILL SENSOR FAULT. See System states.

Changed

What What it means for you

E-Stop cause stays on the banner

After an E-Stop or a low-water cut-off, the banner keeps showing Operator ESTOP or ESTOP - LWCO until you press Reset, even if the button has been released or the tank has refilled. Before, pressing Start or Stop replaced the text.

Very low tank level must persist for half a second

The Precaution - Filling pause now starts only when the tank level has been below about 3 % for 0.5 s. A brief slosh no longer triggers it.

Controls menu order

Controls now leads to Cooling Fan, LCD Screen Heat, Tank Heat, then PURGE. See Where each screen is.

Refill Max Pressure factory setting

20.0 PSI. See Refill pressure calibration.

Removed

What What it means for you

Auxiliary circulation pump

The optional auxiliary circulation pump is no longer supported. Its screen, its three lines on the Status screen and its output are gone.

In the data log

The parameter log gains three columns for the Tank Heat settings (target, hysteresis and delay). The auxiliary pump columns are removed.