Safety

This page collects the hazards that apply to installing, operating, and servicing the TankerTherm 123. Each hazard is also repeated as a safety notice at the step where it applies, so a technician who goes straight to one procedure still sees it.

Safety notices in this manual

Notice Used for

WARNING

A hazard that can cause death or serious injury — electric shock, burns from hot glycol or hot surfaces.

CAUTION

A hazard that can damage the equipment or cause minor injury — for example, starting the boiler before the air purge, or dry-running the refill pump.

IMPORTANT

A required step or condition that is not itself a hazard — for example, obtaining a Warranty Request Number before shipping parts.

NOTE

Background information that helps you understand a procedure or reading.

TIP

Practical advice that makes a task easier.

Qualified personnel

  • Electrical installation and any work at the boiler face must be performed by a licensed electrician in compliance with local electrical codes.

  • Calibration and setpoint changes on the PLC are password-protected and change how the unit protects itself. Make them only if you understand the procedure — see PLC Calibration and PLC Controls and Setpoints.

Electrical hazards

The unit is supplied at 480 V or 600 V 3-phase, depending on SKU. The Stop and E-Stop buttons stop the unit’s outputs; they do not remove power from the supply terminals in the boiler. Only the upstream main disconnect does that.

High voltage at the boiler face — lock out before touching any wire

Before touching any wire at the boiler face: open the upstream main disconnect, lock it out and tag it out, and verify zero voltage with a properly rated meter. This work must be performed by a qualified electrician.

The boiler face exposes the 480 V or 600 V 3-phase supply next to the low-voltage control wiring. Contact with energized 3-phase conductors can be fatal.

Lockout/tagout

Before any work at the boiler face or on the supply wiring:

  1. Open the upstream main disconnect.

  2. Lock out and tag out the disconnect per site procedure.

  3. Verify zero voltage at the boiler with a properly rated meter.

This applies to:

Hot surfaces and hot glycol

Hot surfaces — personal protective equipment required

The distribution manifold and piping operate at up to 190°F (88°C). Always wear heat-resistant gloves when engaging ball valves or connecting/disconnecting tanker lines. Direct contact with the manifold can cause severe burns.

  • Stop the system and let the glycol cool before opening any strainer, fitting, or drain — see Periodic Maintenance.

  • The Tank Temp probe sits in a compression fitting on the storage tank. Withdrawing it with the tank above approximately 20 % lets coolant flow out of the sensor hole — see Temperature probe calibration.

Pressure

  • A 30 PSI pressure relief valve protects the boiler. Do not plug, cap, or adjust it.

  • The PLC stops the refill pump if refill-line pressure exceeds the Max Pressure setting (default 20.0 PSI). Do not raise this setting toward 30 PSI — see Refill pressure calibration.

Protective interlocks

Do not bypass or disable any of the following. Each is described in Specifications — Protection summary.

  • LWCO (Low-Water Cut-Off) sensor — disables the boiler if the storage tank is critically low

  • ECO high-temperature limit switch on the boiler

  • 30 PSI pressure relief valve

  • Fill Time Limit and Refill Pressure cutoffs on the refill pump

  • E-Stop button on the manifold control panel

Emergency stop

The red E-Stop button on the manifold control panel stops the circulation pump, the boiler, and the refill pump, and latches the alarm strobe. The PLC banner reads Operator ESTOP. The E-Stop does not de-energize the unit — use the main disconnect for that.

To recover, release the E-Stop, press Reset, and press Start — see Resolution — Operator ESTOP.

Equipment-damage hazards

These hazards damage the unit rather than injure people. Each is a CAUTION at the step where it applies.

Hazard Consequence Where it applies

Starting the boiler before the air purge is complete

Boiler damage, not covered by warranty

Startup & First Heat Cycle

Running the refill pump dry

The gear-type refill pump can be destroyed by approximately 20 minutes of cumulative dry running. Repeatedly pressing Reset after a REFILL TIMER EXPIRED fault adds to that total.

Refill fault protection

Rotating a bulkhead fitting while tightening

Damaged internal connections; may void the warranty

Installing loose-packed components

Pulling out crating blocking strips carelessly

Damaged distribution plumbing

Unpacking & Setup

Replacing a Remote Output Box fuse with a higher rating

Damaged PLC output drivers or 12 V DC converter

Remote Output Box

Glycol disposal

Drained glycol and wash water must be disposed of in accordance with local environmental regulations.