Troubleshooting

Common issues, diagnostic steps, and resolutions for the TankerTherm 123.

Safety first

If any fault involves electrical components, leaking glycol, or smoke/unusual odors, disconnect power at the main disconnect before investigating. Contact Thermex Systems at 1-800-865-1532 if you are unsure.

System lockout and warning strobe active

The PLC banner identifies the specific lockout cause. Read the banner first, then apply the matching resolution below.

PLC banner Most likely cause

REFILL TIMER EXPIRED

Refill ran longer than the Fill Time Limit — usually drum empty, suction blocked, or refill pump failure

Refill Pressure Too High

Refill pressure exceeded the configured maximum — usually a kinked overflow, closed downstream valve, or transducer issue

REFILL SENSOR FAULT

The refill pressure sensor signal is missing or out of range — usually a broken wire, an unplugged connector, or a failed sensor

Operator ESTOP

Operator E-Stop button was pressed. The banner stays until Reset, even after the button is released

ESTOP - LWCO

LWCO sensor has tripped — tank critically low. The banner stays until Reset, even after the tank has refilled

Resolution — REFILL TIMER EXPIRED

  1. Verify glycol supply in the 55-gallon supply drum — replenish if empty.

  2. Confirm the suction tube/hose is fully submerged and not kinked.

  3. Inspect the suction filter (also referred to as the side-mounted refill-inlet strainer on the unit) for blockage — see Maintenance.

  4. Press the external Reset button on the manifold control panel.

  5. Wait for Resetting- Wait to clear; the strobe turns off and the banner settles at OFF- Ready.

  6. Press Start to resume heating.

If the lockout recurs without the drum being empty, check:

  • Refill pump for mechanical failure or loss of prime

  • Fill Time Limit setting (default 300 s — investigate before raising)

Resolution — Refill Pressure Too High

  1. Inspect the refill line, overflow, and storage-tank vent for kinks or blockages.

  2. Verify any downstream valves on the refill line are open.

  3. Check that the storage-tank overflow drains freely back to the supply drum.

  4. Press Reset. Wait for Resetting- Wait to clear and the banner to settle at OFF- Ready.

  5. Press Start to resume heating.

If the lockout recurs without an obvious mechanical cause, the pressure transducer may need re-zero or the Max Pressure setpoint may be too low — see PLC Calibration — Refill Pressure.

Resolution — Operator ESTOP

  1. Twist or pull the operator E-Stop button on the manifold panel to release it.

  2. Press Reset. Wait for Resetting- Wait to clear and the banner to settle at OFF- Ready.

  3. Press Start to resume heating.

Resolution — ESTOP - LWCO

  1. Replenish coolant in the storage tank (from the supply drum).

  2. Confirm tank level rises on the Status screen; verify LWCO has cleared.

  3. Press Reset. Wait for Resetting- Wait to clear and the banner to settle at OFF- Ready.

  4. Press Start to resume heating.

  5. Follow up with a tank-level calibration check — LWCO and the analog level sensor should agree, and a disagreement here often indicates the level sensor needs recalibration. See Tank Level Calibration.

Resolution — REFILL SENSOR FAULT

The PLC reads refill-line pressure from a 4–20 mA sensor. If the signal stays below 3.5 mA or above 21.0 mA for half a second, the PLC treats the sensor as faulty, stops the refill pump, locks out the unit and latches the strobe. A reading that low or that high cannot come from real pressure; it means the PLC can no longer see the refill pressure.

Qualified electrician required

All electrical connections must be performed by a licensed electrician in compliance with local electrical codes. Disconnect and lock out the power source before beginning any electrical work.

  1. Open the main disconnect, lock it out and tag it out, and verify zero voltage — see Safety.

  2. Inspect the refill pressure sensor’s connector and cable for a loose plug, a broken wire or damage.

  3. Restore power. Press Reset. Wait for Resetting- Wait to clear and the banner to settle at OFF- Ready.

  4. Press Start to resume heating.

If the banner returns as soon as the reset delay ends, the sensor or its wiring has failed. Contact Thermex Systems — see Contact Support.

System will not reach 190°F

Diagnostic steps

  1. Check glycol level — low level may trigger LWCO cutoff.

  2. Check ambient temperature — extreme cold extends warmup time.

  3. Verify no air in system — repeat air-purge procedure if startup was recent.

  4. Check connected load — four tankers at startup may extend warmup.

  5. Verify stage operation on the boiler controller display.

If all stages are firing and the system still cannot reach target:

  • Inspect for glycol leaks around manifold and piping

  • Verify all three electrical phases are present and balanced

  • Check that the Tank Heat target has not been set lower than the temperature you expect (see Tank Heat thermostat)

  • Check that the boiler controller’s target temperature offset is not set negative (see Temperature Control)

Pressure fails to exceed 7 PSI during bypass

This indicates circulation pump wear. See Maintenance — Circulation Pump Seal Replacement.

Unit will not start heating when Start is pressed

Check the PLC banner and the screen on display:

  1. The PURGE screen is displayed. The Start button is ignored while this screen is open. Press F1 to return to the Home screen, then press Start.

  2. The banner reads Enabled - Target Reached. The unit has started; the storage tank is above the Tank Heat target, so the PLC is holding the boiler off. Heating resumes by itself when the tank cools — see Tank Heat thermostat.

  3. The banner reads Refill Disabled. See the next section.

  4. The banner shows a fault and the strobe is on. See System lockout and warning strobe active.

Unit will not start — banner reads Refill Disabled

The Refill Pump Switch is OFF. The indicator lamp shows a single blink & pause.

  1. Turn the Refill Pump Switch (on the HMI panel) to ON.

  2. Confirm the banner changes from Refill Disabled.

  3. Press Start.

Pump churning/gurgling noises continue

Air has not been fully purged. Return to Startup & First Heat Cycle and repeat the air-purge procedure.

I cannot tell how full the storage tank is

The cabinet is enclosed and has no external sight gauge — tank level is reported on the PLC HMI.

  1. From the Home screen, press F1 (no password needed).

  2. Scroll to Tank Level — the value is shown as a percentage.

If the percentage seems wrong (e.g. you just topped up the tank but it does not read near 100 %), the level sensor calibration has drifted. Recalibrate using Tank Level Calibration — the high-point procedure uses the tank’s overflow fitting as the physical "full" reference.

PLC home screen says Precaution - Filling

This is not a fault. The PLC has detected that tank level is very low (~3 %) without LWCO tripping, has paused circulation and heat to avoid dry running, and is allowing the refill pump to catch up. Operation resumes automatically when the tank reaches ~95 %.

If the condition persists for more than several minutes, refill is failing — check the supply drum and refer to Resolution — REFILL TIMER EXPIRED above.

Cooling fan runs continuously or screen heater won’t cycle off

The PLC controls the cooling fan and the LCD screen heater independently, each from its own sensor. Default setpoints:

Function Engage Disengage

Cooling fan

91 °F (33 °C) ambient

86 °F (30 °C) ambient

Screen heater

32 °F (0 °C) at LCD

37 °F (3 °C) at LCD

If behaviour deviates from these setpoints:

  • Verify the affected sensor reads correctly on the Status screen (the Ambient and LCD fields). An obstructed sensor or a stale calibration is the most common cause.

  • Verify the setpoints have not been changed on PLC Controls — Cooling Fan or LCD Screen Heat.

  • If the sensor reading and setpoints look correct but the output behaviour is still wrong, contact Thermex Systems for controller diagnostics.

Contact support

If troubleshooting does not resolve the issue, contact Thermex Systems.