PLC Status Screen
The Expanded Status screen is the single best place to check what the system is doing right now. Press F1 from the home screen — no password required.
|
PLC navigation at a glance
|
Reading the Status screen
Precaution - Filling condition — circulation and heat are paused while the refill pump tops up the tank. The screenshot shows the first five lines of the scrollable list.The Status screen is a scrollable list. Use the on-screen ▲ / ▼ arrows to scroll. The banner at the top of the screen is the current system state — the same banner shown on the Home screen.
The full list of fields, in scroll order, is:
| Field | Format | Meaning |
|---|---|---|
Circulation |
Text |
|
Heat |
Text |
|
Refill Pump |
Text |
|
LWCO |
Text |
|
Tank Level |
Numeric, % |
Tank coolant level as a calibrated percentage. Refill is automatic; with the supply drum kept full there is no need to monitor this value. Calibrated via Tank Level Calibration. |
Tank Temp |
Numeric, °F |
Tank coolant temperature, read from the dedicated PLC tank-temp probe. The Tank Heat thermostat acts on this reading. |
Refill Timer |
Numeric, seconds |
Elapsed seconds in the current refill cycle. Counts up against the Fill Time Limit. |
Refill Pres. |
Numeric, PSI |
Live refill-line pressure. |
Ambient |
Numeric, °C |
Cabinet ambient temperature. Drives the cooling-fan logic. |
Fan |
Text |
|
LCD |
Numeric, °C |
Temperature at the HMI screen itself. Drives the LCD-heater logic. |
LCD Heater |
Text |
|
Version |
ASCII |
PLC software version, for example |
|
Temperatures are shown in two units
The PLC displays Tank Temp in °F, and Ambient and LCD in °C. This is how the controller is programmed. The cooling-fan and LCD-heater setpoints on the Controls screens are also in °C; the Tank Heat settings are in °F. Where this manual quotes a factory default, it gives both units — see Specifications — Enclosure temperature regulation. |
System states
The banner at the top of the Home and Status screens reports the current system state as a literal text string. The same string is recorded in the unit’s event log on every state transition.
The full list of state strings the PLC reports — in order of progression through a normal session — is shown below. State strings are reproduced verbatim, including their (intentional) spacing.
| State | Meaning |
|---|---|
|
Logged once at controller boot. Not a persistent state. |
|
System is in standby, awaiting Start. No outputs energized. |
|
Momentary marker logged at the instant the operator presses Start. Immediately superseded by |
|
System enabled and ramping toward operating temperature. Indicator slow-blinks. |
|
Normal operating state — circulation running and boiler enabled. Indicator solid. |
|
Normal operation, plus the refill pump is topping up the storage tank. |
|
The storage tank is above the Tank Heat target. Circulation keeps running and the PLC holds the boiler off until the tank cools — see Tank Heat thermostat. Indicator slow-blinks. |
|
Momentary marker logged at the instant the operator presses Stop. |
|
Boiler disabled, circulation pump still running through its off-delay. |
|
The circulation pump is running from the PURGE screen with the boiler held off — see Startup & First Heat Cycle. |
|
The operator E-Stop button was pressed. System locked out; strobe latched. The banner stays until Reset is pressed, even after the button is released. |
|
The Low-Water Cut-Off has tripped. System locked out; strobe latched. Replenish coolant before resetting. The banner stays until Reset is pressed, even after the tank has refilled. |
|
Brief hold after pressing Reset while clear-conditions are evaluated. Returns to |
|
System is refilling the storage tank (initial fill or post-drawdown). |
|
Refill pressure exceeded the configured maximum — refill stopped, fault latched. |
|
Refill ran longer than the configured fill time limit — fault latched. |
|
The refill pressure sensor signal is outside its valid range (broken wire, unplugged connector or failed sensor) — refill stopped, fault latched. |
|
Momentary marker logged at the instant the operator presses Reset. |
|
The external refill switch is off — heating is not enabled and the refill pump is locked out. |
|
Tank fell to a near-empty level (below ~3 %) without LWCO tripping. Circulation and heat are paused while the refill pump catches up. Returns to |
|
Why "Precaution" exists
The |
|
Event logging
Every state transition is recorded as an event in the unit’s data log, and the current state is also logged at periodic intervals as a heartbeat. The log is the authoritative record of what the unit was doing at any past moment — useful for diagnosing intermittent issues after the fact. To retrieve the log, see PLC Data Log. |