PLC Status Screen

The Expanded Status screen is the single best place to check what the system is doing right now. Press F1 from the home screen — no password required.

PLC navigation at a glance
  • Home screen — live status: Circ / Heat / Fill / Fault indicators, system state banner, tank temperature, Reset Delay countdown when applicable.

  • F1 — on the Home screen, opens the Expanded Status screen (live readouts, no password). On any other screen, returns to the Home screen and clears the password; you must re-enter it to reach the Menu again.

  • F2 — opens the password prompt. After successful entry, the Menu appears with four sections: Status, Calibration, Output, Controls.

  • Password entry — press F2, tap the centre of the screen to bring up the on-screen number pad, enter 60525, confirm.

  • Esc / back arrow — returns to the previous screen.

  • Up / Down arrows — scroll within a list.

  • Enter (↵) — confirm a selection.

Reading the Status screen

Status screen showing Circulation OFF, Heat OFF, Refill Pump ON, LWCO Normal, Tank Level 2 percent
Figure 1. Status screen during a Precaution - Filling condition — circulation and heat are paused while the refill pump tops up the tank. The screenshot shows the first five lines of the scrollable list.

The Status screen is a scrollable list. Use the on-screen ▲ / ▼ arrows to scroll. The banner at the top of the screen is the current system state — the same banner shown on the Home screen.

The full list of fields, in scroll order, is:

Field Format Meaning

Circulation

Text

ON / OFF — circulation pump output

Heat

Text

ON / OFF — boiler enable output. The boiler may still cycle internally on its own controller even when this is OFF.

Refill Pump

Text

ON / OFF — refill pump output

LWCO

Text

Normal / Low — Low-Water Cut-Off sensor. Low means the tank is empty enough to disable the boiler immediately.

Tank Level

Numeric, %

Tank coolant level as a calibrated percentage. Refill is automatic; with the supply drum kept full there is no need to monitor this value. Calibrated via Tank Level Calibration.

Tank Temp

Numeric, °F

Tank coolant temperature, read from the dedicated PLC tank-temp probe.

Refill Timer

Numeric, seconds

Elapsed seconds in the current refill cycle. Counts up against the Fill Time Limit.

Refill Pres.

Numeric, PSI

Live refill-line pressure.

Ambient

Numeric, °C

Cabinet ambient temperature. Drives the cooling-fan and LCD-heater logic.

Fan

Text

ON / OFF — cabinet cooling-fan output.

LCD

Numeric, °C

Temperature at the HMI screen itself.

LCD Heater

Text

ON / OFF — LCD-screen heater output (cold-weather use).

Aux Pump

Text

Master enable for the auxiliary circulation pump (ENABLED / DISABLED). Set on Aux Circulation Pump.

Aux Setpoint

Numeric, °F

Tank-temperature threshold at which the aux pump enables.

Aux Pump

Text

ON / OFF — current aux pump output state.

Version

ASCII

Firmware version (currently v2.1). Useful when contacting support.

Temperatures are shown in two units

The PLC displays Tank Temp and Aux Setpoint in °F, and Ambient and LCD in °C. This is how the controller is programmed. The cooling-fan and LCD-heater setpoints on the Controls screens are also in °C. Where this manual quotes a factory default, it gives both units — see Specifications — Enclosure temperature regulation.

Two rows labelled Aux Pump

Two adjacent fields share the Aux Pump label on the screen — one is the master enable (ENABLED / DISABLED), the other is the current output state (ON / OFF). Distinguish them by position: the enable appears immediately above Aux Setpoint, the output state immediately below.

The aux pump itself is a special-order option — a 3rd circulating pump driving a separate heating loop. Most units do not have it. If yours does not, these three rows are still shown on the screen but represent no physical pump. See Aux Circulation Pump.

System states

The banner at the top of the Home and Status screens reports the current system state as a literal text string. The same string is recorded in the unit’s event log on every state transition.

The full list of state strings the PLC reports — in order of progression through a normal session — is shown below. State strings are reproduced verbatim, including their (intentional) spacing.

State Meaning

Power Cycle

Logged once at controller boot. Not a persistent state.

OFF- Ready

System is in standby, awaiting Start. No outputs energized.

Start Pressed

Momentary marker logged at the instant the operator presses Start. Immediately superseded by Enabled - Warmup or another state.

Enabled - Warmup

System enabled and ramping toward operating temperature. Indicator slow-blinks.

Enabled-Heating

Normal operating state — circulation running and boiler enabled at temperature. Indicator solid.

Heating - Refilling

Normal operation, plus the refill pump is topping up the storage tank.

Stop Pressed

Momentary marker logged at the instant the operator presses Stop.

Cooldown

Boiler disabled, circulation pump still running through its off-delay.

Operator ESTOP

The operator E-Stop button is depressed. System locked out; strobe latched.

ESTOP - LWCO

The Low-Water Cut-Off has tripped. System locked out; strobe latched. Replenish coolant before resetting.

Resetting- Wait

Brief hold after pressing Reset while clear-conditions are evaluated. Returns to OFF- Ready on success; the operator must press Start to resume heating.

Refilling

System is refilling the storage tank (initial fill or post-drawdown).

Refill Pressure Too High

Refill pressure exceeded the configured maximum — refill stopped, fault latched.

REFILL TIMER EXPIRED

Refill ran longer than the configured fill time limit — fault latched.

Reset Pressed

Momentary marker logged at the instant the operator presses Reset.

Refill Disabled

The external refill switch is off — heating is not enabled and the refill pump is locked out.

Precaution - Filling

Tank fell to a near-empty level (below ~3 %) without LWCO tripping. Circulation and heat are paused while the refill pump catches up. Returns to Enabled-Heating automatically once the tank reaches ~95 %.

Why "Precaution" exists

The Precaution - Filling state protects the boiler from running dry in the gap between tank level dropping below 3 % and LWCO physically tripping. Heat and circulation are paused, the refill pump runs, and operation resumes automatically once the tank refills to 95 %. No operator action is required unless the refill itself fails — in which case the PLC promotes the condition to REFILL TIMER EXPIRED or Refill Pressure Too High and latches the strobe.

Event logging

Every state transition is recorded as an event in the unit’s data log, and the current state is also logged at periodic intervals as a heartbeat. The log is the authoritative record of what the unit was doing at any past moment — useful for diagnosing intermittent issues after the fact. To retrieve the log, see PLC Data Log.