PLC Output Tests

The Output menu lets a service technician test the PLC’s discrete and analog outputs without putting the system into an operational state. Use these tests during commissioning, after wiring changes, or when verifying field-side equipment such as the strobe, the indicator lamp, or a connected SCADA / data-acquisition input.

PLC navigation at a glance
  • Home screen — live status: Circ / Heat / Fill / Fault indicators, system state banner, tank temperature, Reset Delay countdown when applicable.

  • F1 — on the Home screen, opens the Expanded Status screen (live readouts, no password). On any other screen, returns to the Home screen and clears the password; you must re-enter it to reach the Menu again.

  • F2 — opens the password prompt. After successful entry, the Menu appears with four sections: Status, Calibration, Output, Controls.

  • Password entry — press F2, tap the centre of the screen to bring up the on-screen number pad, enter 60525, confirm.

  • Esc / back arrow — returns to the previous screen.

  • Up / Down arrows — scroll within a list.

  • Enter (↵) — confirm a selection.

System should be at standby for output tests

The output tests drive the physical outputs directly, bypassing normal control logic. Stop the system before testing, or be prepared for the unexpected behavior of energizing an output during operation.

Alarm Strobe Output

Drives the strobe output to verify wiring, the strobe itself, and the cable run from the PLC to the manifold control panel.

Alarm Strobe Output test screen with Test and Cancel buttons
Figure 1. Alarm Strobe Output — Test / Cancel
  1. Press F2 from the home screen, enter the password, and select Output → Alarm Strobe.

  2. Press Test. The strobe energizes for the duration the screen is held active.

  3. Press Cancel to drop the output.

Indicator Output

Drives the indicator lamp output. Use to verify the lamp itself, the cable, or the placard alignment after panel work.

Indicator Output test screen with Test and Cancel buttons
Figure 2. Indicator Output — Test / Cancel
  1. Press F2 from the home screen, enter the password, and select Output → Indicator.

  2. Press Test. The indicator energizes for the duration the screen is held active.

  3. Press Cancel to drop the output.

Temperature Analog Output

The PLC provides an analog output that mirrors tank temperature for connection to a remote monitoring or data-acquisition system. Output range is 0–10 V representing 0–200 °F.

Temperature Analog Output screen showing 61 F / 3.0 V live and simulate buttons for 0 and 200
Figure 3. Temperature Analog Output — current value at top, simulate buttons below
Element Meaning

Top reading (°F)

Current tank temperature in degrees Fahrenheit.

Top reading (V)

Current analog output voltage corresponding to that temperature.

Press to simulate: 0

Drives the analog output to 0 V (= 0 °F) for verification on the receiving side.

Press to simulate: 200

Drives the analog output to 10 V (= 200 °F) for verification on the receiving side.

Two-point loop verification

With a SCADA / DAQ system on the receiving end, press 0 and confirm the receiver reports near 0 °F (or 0 V), then press 200 and confirm the receiver reports near 200 °F (or 10 V). This proves the analog loop end-to-end without changing tank conditions.

Simulation drives the live output

Pressing 0 or 200 drives the actual analog output. Any monitoring system or alarm tied to that signal will see the simulated value. Coordinate with whoever is watching the data feed before simulating.

See also