Periodic Maintenance
A consistent maintenance schedule extends equipment life and ensures safe operation. Maintenance tasks are grouped by frequency below.
Maintenance schedule
| Frequency | Task |
|---|---|
Weekly |
Check glycol level in supply drum; replenish before empty |
Monthly |
Clean manifold wye strainer screens and refill suction filter screen |
Twice yearly |
Drain system, flush with water, refill with glycol |
As required |
Replace circulation pump mechanical seal (typically years between replacements) |
Weekly — drum level check
-
Visually verify adequate glycol volume in the 55-gallon supply drum
-
Replenish supply before drum becomes empty
-
Record inspection in maintenance log
Monthly — strainer cleaning
Clean strainer screens on both the distribution manifold (wye strainers) and the refill suction filter.
|
Shut down before servicing strainers
Stop the system and allow piping to cool before removing strainer components. Manifold piping operates at up to 190°F (88°C). |
-
Press the Stop button.
-
Allow the manifold to cool.
-
Close the upstream ball valve at each strainer.
-
Remove the strainer blow-down plug and screen.
-
Clean the screen with clean water and a soft brush.
-
Reinstall the screen and blow-down plug.
-
Reopen ball valves.
-
Repeat for the refill suction filter.
Twice yearly — water flush
A twice-annual water flush removes sediment and degraded glycol residues from the system.
Procedure
-
Press Stop and let the glycol cool before opening any drain.
-
Drain the system completely of glycol.
-
Refill with water only.
-
Purge air using the same procedure as initial startup — see Startup & First Heat Cycle.
-
Operate in bypass mode (no tankers connected) for a minimum of 8 hours.
-
Drain the system again.
-
Refill with fresh glycol.
-
Purge air and return to normal operation.
|
Used glycol disposal
Drained glycol and wash water must be disposed of in accordance with local environmental regulations. |
As required — circulation pump seal replacement
Replace the circulation pump mechanical seal if:
-
Pump becomes noisy during operation, or
-
System pressure fails to exceed 7 PSI during bypass operation
The normal expected service life is years rather than months. Frequent seal failure indicates an underlying issue that should be investigated.
|
Parts information
Refer to the circulation pump parts list (available from Thermex Systems) for part numbers and replacement procedures. Contact 1-800-865-1532 for parts orders. |