Periodic Maintenance

A consistent maintenance schedule extends equipment life and ensures safe operation. Maintenance tasks are grouped by frequency below.

Maintenance schedule

Frequency Task

Weekly

Check glycol level in supply drum; replenish before empty

Monthly

Clean manifold wye strainer screens and refill suction filter screen

Twice yearly

Drain system, flush with water, refill with glycol

As required

Replace circulation pump mechanical seal (typically years between replacements)

Weekly — drum level check

  • Visually verify adequate glycol volume in the 55-gallon supply drum

  • Replenish supply before drum becomes empty

  • Record inspection in maintenance log

Monthly — strainer cleaning

Clean strainer screens on both the distribution manifold (wye strainers) and the refill suction filter.

Shut down before servicing strainers

Stop the system and allow piping to cool before removing strainer components. Manifold piping operates at up to 190°F (88°C).

  1. Press the Stop button.

  2. Allow the manifold to cool.

  3. Close the upstream ball valve at each strainer.

  4. Remove the strainer blow-down plug and screen.

  5. Clean the screen with clean water and a soft brush.

  6. Reinstall the screen and blow-down plug.

  7. Reopen ball valves.

  8. Repeat for the refill suction filter.

Twice yearly — water flush

A twice-annual water flush removes sediment and degraded glycol residues from the system.

Procedure

  1. Press Stop and let the glycol cool before opening any drain.

  2. Drain the system completely of glycol.

  3. Refill with water only.

  4. Purge air using the same procedure as initial startup — see Startup & First Heat Cycle.

  5. Operate in bypass mode (no tankers connected) for a minimum of 8 hours.

  6. Drain the system again.

  7. Refill with fresh glycol.

  8. Purge air and return to normal operation.

Used glycol disposal

Drained glycol and wash water must be disposed of in accordance with local environmental regulations.

As required — circulation pump seal replacement

Replace the circulation pump mechanical seal if:

  • Pump becomes noisy during operation, or

  • System pressure fails to exceed 7 PSI during bypass operation

The normal expected service life is years rather than months. Frequent seal failure indicates an underlying issue that should be investigated.

Parts information

Refer to the circulation pump parts list (available from Thermex Systems) for part numbers and replacement procedures. Contact 1-800-865-1532 for parts orders.