Specifications
Complete technical specifications for the TankerTherm 123 circulating glycol heater.
At a glance
| Specification | Value |
|---|---|
Heater type |
Circulating electric glycol heater with onboard day tank |
Dimensions |
38″ wide × 24″ deep × 50″ high on current units (earlier units are 46″ high) |
Weight |
380 lbs (173 kg) |
Capacity |
123,000 BTU/hr max input (13 °F temperature rise per pass through the boiler @ 19 GPM) |
Power supply |
480 V or 600 V 3-phase, 36 kW (see Voltage variants) |
Control voltage |
12 V DC, supplied by an internal 3-phase-to-12 V DC converter |
Glycol temperature |
Adjustable via digital controller up to 190 °F (88 °C) |
Venting |
Through rear of chassis, temperature controlled, power vented |
Construction |
Powder-coated chassis, designed for outdoor installation |
Controls |
Onboard 2-stage boiler digital controller plus industrial PLC supervisor with integrated touchscreen HMI |
Remote monitoring |
Remote Output Box on rear of unit — Indicator + Strobe (digital 12 V DC, 0.5 A fused) and 0–10 V analog tank temperature (0–200 °F). See Remote Output Box. |
Options |
Auxiliary circulation pump for a separate heating loop (special order). See Auxiliary circulation pump. Deprecated: not supported in later PLC software. |
Voltage variants
This manual covers two SKUs that differ only in voltage. The boiler heating elements and the circulation pump motor are voltage-matched to the supply; all other components are common.
| SKU | Power supply | Notes |
|---|---|---|
|
480 VAC 3-phase, 36 kW |
Standard variant. |
|
600 VAC 3-phase, 36 kW |
High-voltage variant. Heater and circulation pump motor are 600 V matched. Connection block is labelled |
See Power Supply Connections for wiring procedure (identical for both variants — the supply voltage is the only difference).
Performance details
Flow and pressure
| Parameter | Rating |
|---|---|
Pump flow rate |
20 GPM |
Operating pressure range |
5–20 PSI |
Bypass/deadhead pressure |
20 PSI |
Relief valve setting |
30 PSI |
Controls
-
Boiler controller — ASME boiler with digital 2-stage temperature modulation, with a user-adjustable ±10 °F target offset (see Temperature Control)
-
PLC supervisor — industrial PLC with integrated touchscreen HMI (software v2.1) — see PLC Controller Overview
-
Glycol level control — Automatic, with low-level refill activation; tank level visible on the PLC Status screen
-
Enclosure temperature — Cooling fan and screen heater regulated by the PLC against ambient temperature setpoints
-
Connected tankers — Up to four at once, filled in succession and heated together
Protection summary
| Protection | Action |
|---|---|
LWCO (Low-Water Cut-Off) |
Hardware sensor disables boiler immediately if tank coolant is critically low; latches strobe; requires Reset |
ECO high-temperature limit |
Hardware over-temperature switch on the boiler |
30 PSI relief valve |
Boiler over-pressure protection |
Fill Time Limit |
PLC stops refill pump, latches strobe, and locks out the system if a single refill cycle exceeds the configured time (default 300 s). This is how the unit protects the refill pump when the supply drum runs dry. |
Refill Pressure cutoff |
PLC stops refill pump and latches strobe if refill pressure exceeds the configured maximum (default 25.0 PSI) |
Precaution Disable |
PLC pauses circulation and heat at very low tank level (~3 %) to avoid dry running while refill catches up |
Safety features
|
Critical safety systems
The TankerTherm includes multiple interlocks. Do not attempt to bypass or disable any of the following:
|
Enclosure temperature regulation
|
Screen heater deprecated
The screen heater is deprecated. Current units are built without it; the cooling fan is unchanged. |
The PLC regulates two independent enclosure functions: a cooling fan that ventilates the cabinet in hot weather, and a screen heater that keeps the LCD HMI warm in cold weather. Each is controlled from its own temperature sensor.
-
Engages at 91 °F (33 °C)
-
Disengages below 86 °F (30 °C)
-
Engages at 32 °F (0 °C)
-
Disengages above 37 °F (3 °C)
Setpoints are field-adjustable — see PLC Controls and Setpoints.