PLC Controls and Setpoints

The Controls menu holds the adjustable setpoints that are not part of a calibration routine — the cooling-fan and LCD-screen-heater setpoints and the Tank Heat thermostat — and the PURGE screen used for the air purge. This page also covers the fill time limit, which is part of the refill protection logic and is reached through the Calibration menu. Read its section before changing it.

The Controls screens are a chain. Press F2 from the home screen, enter the password, and select Controls: the first screen opens. Use the next and previous arrows on each screen to move along the chain.

Screen How to reach it

Cooling Fan

Menu → Controls

LCD Screen Heat

Menu → Controls → next

Tank Heat

Menu → Controls → next twice

PURGE

Menu → Controls → next three times

Fill Time Limit

Menu → Calibration → Tank → next twice (after TANK LOW % CAL and TANK High % CAL)

PLC navigation at a glance
  • Home screen — live status: Circ / Heat / Fill / Fault indicators, system state banner, tank temperature, Reset Delay countdown when applicable.

  • F1 — on the Home screen, opens the Expanded Status screen (live readouts, no password). On any other screen, returns to the Home screen and clears the password; you must re-enter it to reach the Menu again.

  • F2 — opens the password prompt. After successful entry, the Menu appears with four sections: Status, Calibration, Output, Controls.

  • Password entry — press F2, tap the centre of the screen to bring up the on-screen number pad, enter 60525, confirm.

  • Esc / back arrow — returns to the previous screen.

  • Up / Down arrows — scroll within a list.

  • Enter (↵) — confirm a selection.

Cooling fan

The PLC switches the cabinet cooling fan from the cabinet ambient temperature probe. The fan turns on when ambient temperature reaches the High setpoint and stays on until it falls to the Low setpoint. The gap between the two setpoints keeps the fan from switching on and off rapidly around a single temperature.

Cooling Fan screen showing 15 C ambient, Low 30, High 33, Delay 30 SEC, and a Jog Fan button
Figure 1. Cooling Fan — Low 30 °C, High 33 °C, 30 s delay, with a Jog Fan test
Field Meaning

Low

Ambient temperature (°C) at or below which the fan turns off. Default 30 °C (86 °F).

High

Ambient temperature (°C) at or above which the fan turns on. Default 33 °C (91 °F).

Delay

Minimum delay between state changes (default 30 s) — prevents short-cycling near the setpoint.

Jog Fan

Manual fan run for verification — energizes the fan output for a brief test. Use during commissioning or after maintenance.

Verifying the fan after maintenance

After cleaning or replacing the cooling fan, verify it before returning the unit to service:

  1. Open the Cooling Fan screen.

  2. Press Jog Fan.

  3. Confirm the fan runs, which verifies its wiring, and that it turns in the same direction as before.

LCD screen heater

Deprecated

The LCD screen heater is deprecated. Current units are built without it. On a unit without the heater, the LCD Screen Heat screen and the LCD Heater line on the Status screen are still shown but have no effect.

The HMI display is heated in cold weather to keep the LCD readable and within its operating temperature. The PLC switches the heater from the temperature sensor at the HMI screen: the heater turns on at the Low setpoint and off at the High setpoint, with a delay between state changes.

LCD Screen Heat screen showing 16 C measured, Low 0, High 3, and Delay 30 SEC
Figure 2. LCD Screen Heat — Low 0 °C, High 3 °C, 30 s delay
Field Meaning

Low

LCD temperature (°C) at or below which the heater is on. Default 0 °C (32 °F).

High

LCD temperature (°C) at or above which the heater is off. Default 3 °C (37 °F).

Delay

Minimum delay between state changes (default 30 s). The PLC accepts up to 60 s.

Tank Heat

The Tank Heat screen sets the PLC thermostat that holds the boiler off once the storage tank is above its target temperature. The screen shows the live tank temperature.

Field Range Default Meaning

Target

80–195 °F

195 °F

Tank temperature above which the PLC holds the boiler off.

Hysteresis

1–50 °F

10 °F

How far the tank must cool below Target before the boiler is allowed to run again.

Delay

Up to 60 s

1 s

How long the tank must stay below Target minus Hysteresis before the boiler is allowed to run again.

While the thermostat is holding the boiler off, the banner reads Enabled - Target Reached. How the thermostat works with the boiler’s own controller, and how to change a setting, are described in Temperature Control — Tank Heat thermostat.

PURGE

The PURGE screen runs the circulation pump by itself, with the boiler held off, to push entrapped air out of the circulation loop and into the vented storage tank. Use it at first startup and after every drain and refill.

On the screen Meaning

Start Circ Pump

Starts the circulation pump. Works only when the unit is stopped and no fault or reset delay is active.

Stop Circ Pump

Stops the circulation pump.

Pump Running

Shows whether the circulation pump output is on.

Status line

The current system state — Purging while the pump is running from this screen, or Refilling while the refill pump is also running.

While the screen is displayed, the Start button is ignored and the boiler cannot come on. The pump stops when you leave the screen, including when the password times out 5 minutes after it was entered. The full procedure is in Startup & First Heat Cycle.

Fill time limit

The fill time limit caps how long the refill pump may run continuously before the PLC declares a REFILL TIMER EXPIRED fault, latches the strobe, and locks out the system. This protects the unit from running the refill pump indefinitely on an empty supply drum, a kinked suction line, a stuck float, or a leak.

Fill Time Limit screen showing 300 seconds
Figure 3. Fill Time Limit — default 300 seconds
Field Range Default Meaning

Time limit

60–500 s

300 s (5 minutes)

Maximum continuous refill-pump run time. If exceeded, the PLC stops the refill pump, energizes the strobe, and locks out the system.

Do not raise the fill time limit to work around recurring timeouts

A longer limit lets the gear-type positive-displacement refill pump run dry for longer before the fault trips, and it hides whatever is slowing the refill. The pump’s dry-running tolerance is approximately 20 minutes cumulative before pump damage.

If refill cycles are regularly approaching the 300 s limit, check for:

  • A nearly-empty supply drum (replenish)

  • A kinked or partially blocked suction line

  • A clogged suction filter (the side-mounted refill-inlet strainer)

  • A stuck or sluggish refill pump

  • A pressure-side restriction triggering the pressure cutoff before fill completes

If the fill time limit trips

The PLC banner reads REFILL TIMER EXPIRED. Correct the cause, press Reset, wait for the banner to settle at OFF- Ready, and press Start. Step-by-step instructions are in Troubleshooting — Resolution — REFILL TIMER EXPIRED.

See also