What Changed Since Software v2.1
This page is for anyone who knows a unit on PLC software v2.1 and is now working with v2.2 — for example after a software update. It lists what is different. The rest of this manual describes v2.2 as it is.
To check which software a unit runs, read the Version line on the Status screen — see Which manual matches my unit?.
Added
| What | What it means for you |
|---|---|
PURGE screen |
The air purge is now run from the PLC. You no longer open the boiler cover or disconnect the boiler control wire. See Startup & First Heat Cycle. |
Tank Heat thermostat |
A new screen sets a tank-temperature Target (80–195 °F). Above the target the PLC holds the boiler off and the banner reads |
Refill pressure sensor fault |
A broken wire, an unplugged connector or a failed refill pressure sensor now stops the unit with the banner |
Three new system states |
|
Changed
| What | What it means for you |
|---|---|
E-Stop cause stays on the banner |
After an E-Stop or a low-water cut-off, the banner keeps showing |
Very low tank level must persist for half a second |
The |
Controls menu order |
Controls now leads to Cooling Fan, LCD Screen Heat, Tank Heat, then PURGE. See Where each screen is. |
Refill Max Pressure factory setting |
20.0 PSI. See Refill pressure calibration. |