Refill System Operation
The refill system keeps the internal 10-gallon storage tank filled from the external 55-gallon supply drum. After the Initial System Fill, it runs automatically as long as the Refill Pump Switch is ON and the supply drum has glycol in it.
This page covers three topics:
-
Automatic refill — how the PLC keeps the storage tank filled, including Precaution mode
-
Refill fault protection — the time and pressure limits that stop the refill pump
-
Restoring operation after a refill lockout — what to do after a refill fault locks out the system
Automatic refill
Refill Pump Switch
The switch labelled REFILL PUMP on the HMI panel enables the automatic refill system. On current units it is a rotary selector below the PLC HMI; on earlier units it is a toggle above the HMI. It does not run the pump directly — the PLC decides when the pump runs.
| Position | Effect |
|---|---|
|
Normal operating position. The PLC runs the refill pump automatically based on storage tank level. |
|
The refill system is disabled and heating is not enabled. The PLC banner reads |
Refill cycle
| Trigger | System response |
|---|---|
Storage tank level falls below 50 % |
Refill pump starts. The PLC banner reads |
Storage tank level reaches 95 % |
Refill pump stops. |
The top 5 % of the storage tank is left empty on purpose. Glycol expands as it heats to 190 °F, and that space absorbs the expansion. Any overflow drains back to the supply drum through the red vent hose.
Precaution mode at very low tank level
The LWCO (Low-Water Cut-Off) is a hardware sensor in the storage tank. If it detects that the tank is critically low, it disables the boiler immediately and the PLC latches an ESTOP - LWCO fault, which needs an operator reset — see Resolution — ESTOP - LWCO.
Precaution mode is designed to act before that happens. If storage tank level drops below approximately 3 % while the system is enabled, and the LWCO has not tripped, the PLC enters Precaution - Filling:
-
Circulation and heat are paused.
-
The refill pump runs.
-
Operation resumes automatically once the storage tank reaches 95 %.
No operator action is required unless the refill itself fails — in which case the PLC raises one of the refill faults below.
Refill fault protection
The PLC stops the refill pump and locks out the system on either of two refill faults. Both latch the alarm strobe and require an operator reset.
|
Do not run the refill pump dry
The refill pump is a gear-type positive-displacement pump. Approximately 20 minutes of cumulative dry running can destroy it. Pressing Reset without correcting the cause adds to that total. Always replenish the supply drum or correct the cause before resetting. |
Fill Time Limit — REFILL TIMER EXPIRED
The Fill Time Limit (default 300 s / 5 minutes) caps how long a single refill cycle can run. If the supply drum becomes empty during a refill cycle:
-
The refill pump continues running until the Fill Time Limit expires.
-
The PLC shuts the refill pump off.
-
The alarm strobe energizes.
-
The PLC banner reads
REFILL TIMER EXPIRED. -
The entire system locks out.
The default of 300 s keeps a single fault well below the pump’s dry-running tolerance. The Fill Time Limit is adjustable on the PLC — see PLC Controls — Fill Time Limit. Raising it is rarely the right answer; investigate the underlying cause first.
Refill pressure — Refill Pressure Too High
The PLC monitors refill-line pressure with a 4–20 mA / 0–30 PSI transducer. The limit is the Max Pressure setting (default 20.0 PSI). It protects the storage tank and refill plumbing from over-pressurization caused by a kinked overflow, a closed downstream valve, or a fully-pressurized tank that the high-cal point has missed. If refill pressure exceeds the limit:
-
The PLC stops the refill pump immediately.
-
The alarm strobe energizes.
-
The PLC banner reads
Refill Pressure Too High. -
The entire system locks out.
See PLC Calibration — Refill Pressure for adjustment and zero calibration.
Refill pressure sensor — REFILL SENSOR FAULT
The PLC also checks that the refill pressure sensor itself is working. If the sensor signal is below 3.5 mA or above 21.0 mA for half a second — a broken wire, an unplugged connector or a failed sensor — the PLC can no longer see refill pressure:
-
The PLC stops the refill pump.
-
The alarm strobe energizes.
-
The PLC banner reads
REFILL SENSOR FAULT. -
The entire system locks out.
Restoring operation after a refill lockout
A hard lockout (REFILL TIMER EXPIRED, Refill Pressure Too High, REFILL SENSOR FAULT, or either ESTOP state) drops the system out of the heating state. Unlike Precaution mode — which resumes automatically when the refill catches up — recovery from a hard lockout requires an operator-driven restart.
-
Replenish glycol in the supply drum (or correct the underlying cause for non-dry-run faults — see Troubleshooting).
-
Press the external Reset button on the manifold control panel.
-
Wait for the
Resetting- Waitbanner to clear. The strobe turns off and the banner settles atOFF- Ready. -
Press the external Start button to resume heating.
Weekly inspection requirement
Prevent dry-run lockouts by inspecting the supply drum weekly:
-
Visually check the glycol volume in the supply drum
-
Confirm the drum holds enough glycol for the tanker connections you expect before the next check
-
Replenish before the drum becomes empty
|
Estimating glycol use
Each connected tanker draws the storage tank down by 3–5 gallons, which the refill pump replaces from the supply drum. Multiply by the number of tanker connections you expect per week to gauge how often the drum needs replacing. |